Add to Cart
2V VRLA Solar Gel batteries for Emergency System and UPS Systems(2V 500Ah)
Amaxpower CL Series 2V 500ah VRLA Gel batteries Solar Battery For Telecom System and UPS System
Amaxpower CL Series of 2V Gel Battery are Stable quality & high reliability for industry battery,Sealed construction for AGM Battery,Long service life,Maintenance Free operation for VRLA Battery.
AMaxpower 2V long service Series delivers trouble free ultra-long life, with a designed life of 20 years. Specially designed Calcium lead alloys for positive and negative grid, provides better current conductivity to the terminals with lower internal resistance. Presence of optimum levels of Tin, calcium, and aluminum along with special grain refiners ensure a long-performance.
Applications of CL Sereis 2V Deep Cycle Gel Batteries :
|
|
Nominal Voltage | 2V (Single cell) | |
Nominal Capacity | 500Ah@10 hour-rate | |
Dimension | Length | 241±2(9.49 inches) |
Width | 172±2(6.77 inches) | |
Height | 331±2(13.0 inches) | |
Total Height | 366±2(14.41 inches) | |
Weight | Approx. 28kg (61.7lbs) | |
Reference Capacity (25°C/77°F ) | 20 hour rate (26.3A) | 525Ah |
10 hour rate (50A) | 500Ah | |
5 hour rate (90A) | 450Ah | |
3 hour rate (133.3A) | 400Ah | |
1 hour rate (325A) | 325Ah | |
Max. Discharge Current (25°C/77°F) | 2500A (5S) | |
Internal Resistance | Full charged at 25℃(77°F): Approx. 0.8mΩ | |
Charge (Constant Voltage) (25°C/77°F) |
Cycle Use |
Voltage: 2.33-2.37V@25℃(77°F) Initial Charging Current: Less than 100A |
Float Use | Voltage: 2.24-2.28V@25℃(77°F) | |
Operating Temperature Range | Discharge | -20~60°C |
Charge | -10~60°C | |
Storage | -20~60°C | |
Nominal Operating Temperature Range | 25°C ±3°C(77±3°F) | |
Capacity affected by Temperature (20 hour rate) |
40°C(104°F) | 102% |
25°C(77°F) | 100% | |
0°C(32°F) | 85% | |
-15°C(5°F) | 65% | |
Self-Discharge (25°C/77°F) | After 3 month | 91% |
After 6 month | 82% | |
After 12 month | 64% | |
Container Material | ABS Plastic |
Industry use, Communication equipment, Telecommunication control equipment; Emergency systems; Electric power systems; Golf carts; Caravan; Power station; Nuclear power station; Solar power and wind power systems; Load leveling and storage equipment; Marine equipment; Power generation plants; Alarm systems, UPS and inverters; Medical equipment; Fire and security systems, Control equipment; Stand-by electric power.